The Dwyer SERIES DFMT Digital Paddlewheel Flow Transmitter provides instantaneous, as well as totalizing flow monitoring. The unit offers a user selectable 4 to 20 mA or pulse output with compact display.
Product Applications
- Cooling water monitoring
- Cooling towers
- Chemical proportioning or blending
- Industrial water & wastewater treatment
- Fluctuating fluid conductivity applications
- Reverse osmosis systems
Service : Compatible clean liquids.
Range : See sku chart on catalog page.
Wetted Materials : Sensor and impeller: PVDF; Shaft: Ceramic; O-rings: Fluoroelastomer.
Accuracy : ±1.5% FS.
Repeatability : ±0.5% FS.
Output : Analog: 4 to 20 mA (750 Ω max. loop resistance); Pulse: NPN square wave output; Frequency: 0 to 2 kHz (adjustable); Pulse width: 0 to 1000 ms (adjustable).
Electrical Connections : Removable screw terminal.
Temperature Limits : Process: -4 to 194°F (-20 to 90°C); Ambient: -4 to 149°F(-20 to 65°C).
Pressure Limit : 145 psi (1.0 MPa).
Power Requirements : 12 to 24 VDC.
Power Consumption : 2 W.
Display : 2.38 x 1.25″ (60.33 x 31.75 mm) LCD.
Totalizing Display Maximum : 9,999,999,999.
Process Connection : See sku chart on catalog page.
Enclosure Rating : IP65.
Enclosure Material : ABS plastic.
Weight : See sku chart on catalog page.