Positive, negative and differential pressures can be measured within a full span accuracy of ±0.25 with the Series 616W Differential Pressure Transmitter. Units are enclosed in a polycarbonate case, rated NEMA 4X (IP66) and operate by sensing the pressure of air and compatible gases then sending a standard 4-20 mA output signal. Design enables operation in 2-wire current loops. A wide range of models are available factory calibrated to specific ranges. The span and zero controls are for use when checking calibration. They are not intended for re-ranging to a significantly different span. The LCD display allows local indication of pressure.
Product Applications
- Dust collection
- Outdoor HVAC
- Roof-top equipment
Service : Air and non-combustible, compatible gases.
Wetted Materials : Consult factory.
Accuracy : ±0.25% FS @ 77°F (25°C), display accuracy ±0.5%.Stability:±1% FS/yr.
Temperature Limits : 14 to 185°F (-10 to 85°C).
Pressure Limits : See sku chart on catalog page.
Power Requirements : 10 to 35 VDC (2-wire), 17 to 36 VDC, or isolated 21.6 to 33 VAC (3-wire).
Output Signal : 4 to 20 mA (2-wire), 0 to 5 VDC, or 0 to 10 VDC (3-wire).
Zero and Span Adjustments : Push buttons.
Loop Resistance : Current output: 0 to 1250 Ω max; Voltage output: Load resistance 1 kΩ (min).
Current Consumption : 40 mA (max).
Electrical Connections : 3-wire removable European style terminal block for 16 to 26 AWG.
Process Connections : Barbed, dual size to fit 1/8″ and 3/16″ (3.12 and 4.76 mm) ID rubber or vinyl tubing.
Enclosure Rating : NEMA 4X (IP66).
Mounting Orientation : Any orientation.
Weight : Without LCD 8.8 oz (249 g); with LCD 9.6 oz (272 g).
Agency Approvals : CE.