The Series 616KD-LR Differential Pressure Transmitter – Low Ranges is designed for simplicity, making it the ideal choice for installers and maintenance professionals. These low range instruments not only alleviate cumbersome turn pots typically found in most transmitters, but eliminate entirely the need to span the instruments during calibration. With single digital push button, both ZERO AND SPAN are calibrated properly, nothing else is required. No additional reference pressure sources or separate calibration devices are necessary.
Product Applications
- Air handlers
- Variable air volume
- Duct pressure
- Filter monitoring
Service : Air and non-combustible, compatible gases.
Wetted Materials : Consult factory.
Accuracy : ±0.25% FS for ±0.4″ (100 Pa) and ±0.5″ (125 Pa), ±0.5% FS for ±0.25″ (60 Pa), and ±1% FS for ±0.1″ (25 Pa).
Stability : ±1% / year FSO.
Temperature Limits : 0 to 140°F (-17.8 to 60°C).
Pressure Limits : 1 psi max., operation; 10 psi burst.
Power Requirements : 10 to 35 VDC (2 wire), 17 to 36 VDC or isolated 21.6 to 33 VAC (3 wire).
Output Signal : 4 to 20 mA (2-wire), 0 to 5 VDC, 0 to 10 VDC (3-wire).
Response Time : 2.5 Hz sample rate.
Zero and Span Adjustments : Push buttons.
Loop Resistance : Current Output: 0 to 1250Ω max; Voltage Output: Min. load resistance 1kΩ.
Current Consumption : 40 mA max.
Electrical Connections : Screw type terminal block.
Process Connections : Barbed, dual size to fit 1/8″ & 3/16″ (3 mm & 5 mm) ID rubber or vinyl tubing, or 1/4″ NPT.
Enclosure Rating : NEMA1 (IP20).
Mounting Orientation : Vertical with pressure connections pointing down.
Weight : 1.8 oz (51 g).
Agency Approvals : CE, optional plenum rated units meet UL Standard 2043.