sku: PD603-6R0-0 Product Type: 1/8 DIN Process Digital Panel Meter Input: Current (4-20 mA), Voltage (0-10 V) Power: 85-265 VAC, 90-265 VDC Approvals: CE, UL/C-UL Transmitter Power: None Display Category: LED, Single Line, Sunlight Readable Display: 0.56″ High, 4 Digits, Red LED Warranty: 3 years Product Series: Sabre Product Family: PD603 Product category: Digital Panel Meters Product Application: Level, Pressure, Process
Wiring Diagram:
General
Display: 0.56″ (14.2 mm) red LED, 4 digits (-1999 to 9999) Front Panel: NEMA 4X, IP65; panel gasket provided Programming Methods: Four front panel buttons Display Update Rate: 5/sec Overrange: Display flashes 9999 Underrange: Display flashes -1999 Recalibration: All inputs are calibrated at the factory; recalibration is recommended at least every 12 months Max/Min Display: Stored until reset by user or meter is turned off Password: Restricts modification of programmed settings Non-Volatile Memory: Settings stored for a minimum of 10 years Power Options: 85-265 VAC, 50/60 Hz; 90-265 VDC, 20 W max or 12-36 VDC; 12-24 VAC, 6 W max Required Fuse:UL Recognized, 5 A max, slow-blow; up to 6 meters may share one fuse Normal Mode Rejection: 64 dB at 50/60 Hz Isolation: 4 kV input/output-to-power line; 500 V input-to-24 VDC supply Operating Temperature: 0 to 65°C Storage Temperature: -40 to 85°C Relative Humidity: 0 to 90% Connections: Removable screw terminal blocks accept 12 to 22 AWG. Note: RJ11 header for factory use only Enclosure: 1/8 DIN, high impact plastic, 94V-0, color; gray Weight: 8.5 oz (241 g) UL File Number: E160849; 508 Industrial Control Equipment Warranty: 1 year parts & labor
Process Inputs
Inputs: Field selectable: 0-20 mA, 4-20 mA, 0-5, 1-5 V, ±10 V Accuracy: ±0.05% FS ±1 count Function: Linear Decimal Point: Up to 3 decimals: d.ddd, dd.dd, ddd.d, or dddd Calibration: Scale without signal or calibrate with signal source Calibration Range: User programmable over entire range of meter Input Impedance: Voltage range: greater than 1 MΩ Current Range: 50-100 Ω, varies with resettable fuse impedance Input Overload: Protected by auto-resettable fuse Temperature Drift: ±50 PPM/°C Transmitter Supply: Isolated, P+, P-: 24 VDC ±10% @ 200 mA max HART Transparency: Analog input will not interfere with existing HART communications on the wired 4-20 mA signal