The compact Deltapilot FMB50 transmitter with the condensate resistant Contite measuring cell is typically used in the process and hygienic applications.
It is made for level measurement in liquid and paste-like media in open or closed containers and unaffected by possible foam formation. For use in SIL2 safety systems.
- Hermetically sealed Contite measuring cell with condensate-resistance, high reference accuracy: ±0.2%, optionally ±0.1% and minimum temperature effects
- Modular concept for easy replacement of display or electronics
- Seamless and independent system integration (HART/PA/FF)
- Easy menu-guided commissioning via local display, 4 to 20mA with HART, PROFIBUS PA, FOUNDATION Fieldbus
- International usage thanks to a wide range of approvals
For level and/or pressure measurement.
- Process connections: Thread, flanges and flush-mounted hygienic connections
- Process temperature: –10 to +100°C (14 to 212°F) (+135°C (275°F) for 30 minutes maximum)
- Measuring range: 0.1 to 10bar (1.5 to 150psi)
- Accuracy: ±0.2%, ±0.1% (option)
- International explosion protection certificates, overfill prevention WHG, SIL, hygienic certificates
Measuring principle
Hydrostatic
Characteristic / Application
Pressure transmitter for hydrostatic level measurement with flush mounted metallic CONTITE measuring cell:
– hermetically welded
– absolute condensation tight
– climate-resitant
– long-term stable
– Lowest temperature influencesCompact version
Specialities
Modularity to differential pressure and process pressure devices (replacable display, universal electronics)
diagnostic functions
Hermetically sealed Contite measuring cell (condensate-resistant and climatic-proofed)
Supply / Communication
4…20mA HART:
10,5…45V DC
Ex ia: 10,5…30V DC
PROFIBUS PA /
FOUNDATION Fieldbus:
9…32V DC (Non Ex)Accuracy
Standard 0,2%
Optional 0,1%Long term stability
0,05% of URL/year
Ambient temperature
-40°C…85°C
(-40°F…185°F)Process temperature
-10°C…100°C
(14°F…212°F)Process pressure absolute / max. overpressure limit
40 bar (600 psi)
Pressure measuring range
100mbar…10bar
(1.5psi…150psi)Main wetted parts
Alloy C
316L
optional coating AuPtProcess connection
Thread:
G1 1/2, MNPT1 1/2
Flange:
DN40…DN100,
ASME 1 1/2″…4″,
JIS 10K
Process connection hygienic
Tri-Clamp
DIN11851
DIN11864-1
NEUMO
Varivent N
SMS
DRD
Max. measurement distance
100m (328ft) H2O
Communication
4…20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
Certificates / Approvals
ATEX, FM, CSA, CSA C/US, IEC Ex, INMETRO, NEPSI
Safety approvals
Overfill prevention WHG
SIL
Design approvals
EN10204-3.1
NACE MR0103Hygienic approvals
3A, EHEDG
CoC ASME-BPEMarine approval
GL/ ABS/ LR/ BV/ DNV
Drinking water approvals
KTW/ NSF/ ACS
Options
Separate housing
Initial device settings
Overvoltage protectionApplication limits
If pressurized, usage of two pressure transmitters to measure the differential pressure (electronic dP)
Observe ratio head pressure : hydrostatic pressure
Datasheet: Weld-in adapter, process adapter and flanges