  • The range of applications extends from monitoring levels in sewage treatment plants and process water tanks to applications for loading, storage and buffer tanks. FMU30 ultrasonic sensor offers proven software algorithms and all warning and alarm messages are shown on the four-line plain text display and guarantee fast remedy of problems. The envelope curve can also be shown on the display. As the analysis results are displayed directly on-site, this ensures quick and accurate error diagnostics.

    • Quick and simple commissioning via menu-guided onsite operation with four-line plain text display, 7 languages selectable
    • Envelope curves on the on-site display for simple diagnosis
    • Linearization function (up to 32 points) for conversion of the measured value into any unit of length, volume or flow rate
    • Non-contact measurement method minimizes service requirements
    • Installation possible from thread G 1½ or 1½ NPT upwards
    • Integrated temperature sensor for automatic correction of the temperature dependent sound velocity

    Two-wire instrument for continuous non-contact level and flow measurement.

    • Process connection: Thread
    • Temperature: -20 to +60°C (-4 to +140°F)
    • Pressure: +0.7 to +3bar (+10 to +44psi)
    • Maximum measuring distance: 
      Sensor 1½” for liquids 5m (16ft) and for bulk solids 2m (6.6ft), 
      Sensor 2″ for liquids 8m (26ft)and for bulk solids 3.5m (11ft)
    • Blocking distance: 
      Sensor 1½” 0.25m (0.8ft), 
      Sensor 2″ 0.35m (1.15ft)
    • International explosion protection certificates
    • Measuring principle

      Ultrasonic

    • Characteristic / Application

      Compact ultrasonic transmitter

    • Supply / Communication

      2-wire

    • Accuracy

      +/- 3 mm or +/- 0,2 % of set measuring range

    • Ambient temperature

      -20 °C … 60 °C 

      (-4 °F … 140 °F)

    • Process temperature

      -20 °C … 60 °C 

      (- 4°F … 140 °F)

    • Process pressure absolute / max. overpressure limit

      0.7 bar … 3 bar abs

      (10 psi … 44 psi)

    • Main wetted parts

      PP/EPDM

    • Process connection

      G / NPT 1 1/2″ 

      G / NPT 2″

    • Blocking distance

      1 1/2″: 0.25 m (0.8 ft)

      2″:0.35 m (1.15 ft)

    • Application
       
    • Max. measurement distance

      Sensor 1-1/5″: 5m (16 ft)

      Sensor 2″ : 8m (26ft)

    • Communication

      4…20 mA

    • Certificates / Approvals

      ATEX, CSA C/US, IEC Ex, NEPSI

    • Options

      Accessory Enclosed:

      UNI flange 2″ … 4″

    • Application limits

      For higher resistance:

      FMU41/42/FDU9x

      Foam / high turbulence possible:

      FMU42/FDU91

      Fast filling and discharging rate:

      FMU90 + FDU9x

      Level limit detection:

      FMU90 + FDU9x