E&H Liquiphant FTL50 Vibronic Point level detection

Part Number: FTL50 Categories: ,
  • Email Us: sales@celectric.com.my
  • WhatsApp Us: +60165519084
  • Liquiphant FTL50 is a point level switch for use in hazardous areas with all international certificates. Useable in all industries. FTL50 offers functional safety SIL2/SIL3. With the second line of defense the highest degree of safety and availability of the device can be guaranteed. Reliable measurement values, not affected by: changing media properties, flow, turbulences, gas bubbles, foam, vibrations or build-up.

    • Use in safety systems requiring functional safety to SIL2/SIL3 in accordance with IEC 61508/IEC 61511-1
    • International explosion protection certificates and overfill prevention certificate (WHG)
    • No calibration required, easy to start up
    • No mechanically moving parts: no maintenance, no wear, long operating life.
      Monitoring of fork for damage: guaranteed function
    • Second line of defense to protect the environmental
    • Variety of standardized process connections for all applications
    • Stainless steel (316L) and high-corrosion resistant sensor material (Alloy)

    Point level switch for all liquids with completely welded housing concept.

    • Process connections: Threads, flanges and hygienic process connection (Tri-Clamp, dairy coupling, aseptic, DRD, SMS, Varivent)
    • Temperature: -50 to +150°C (-58 to +302°F)
    • Pressure: -1 to +64bar (-14.5 to +928psi)
    • Sensor material: 316L
    • International explosion protection certificates, overfill prevention WHG, SIL, hygienic certificates, marine approval
    • Measuring principle

      Vibration Liquids

    • Characteristic / Application

      Liquiphant M Density
      with Density Computer FML621
      Temperature and pressure measurement

      Modular & completely welded housing concept

      Focus Food & Pharma

      Surface up to 0.3 µ

    • Supply / Communication

      Transmitter power supply (MUS)

    • Ambient temperature

      -50…70°C

      -50…60°C for hazardous applications

    • Process temperature

      0…80°C (validity of accuracy data)

      -50…0°C/80…150°C (with reduced technical data)

    • Process pressure absolute

      0…25 bar

      >25…64 bar (with reduced technical data)

    • Wetted parts

      316L

    • Hygienic

      3A

      EHEDG

    • Sensor length

      Compact: 50.5 mm

    • Output

      Pulse

    • Certificates / Approvals

      ATEX, FM, CSA C/US, IEC Ex, TIIS, INMETRO, NEPSI

    • Specialities

      Commissioning with ReadWin2000

    • Components

      Density Computer FML621

    • Other approvals and certificates

      SIL2/ SIL3

    Datasheet: Weld-in adapter, process adapter and flanges

    Liquiphant M FTL51C Technical Information

    Liquiphant M FTL50, FTL51, FTL50H, FTL51H Technical Information

    Technical Information Liquiphant M Density and Density Computer FML621