Last Updates: 16/08/2020

E&H Deltapilot FMB70 Hydrostatic Level measurement

Part Number: FMB70 Categories: ,
  • Email Us: sales@celectric.com.my
  • WhatsApp Us: +60165519084
  • The Deltapilot FMB70 with the condensate resistant Contite measuring cell and two-chamber housing is typically used in the process and hygienic applications. It is made for level measurement in liquid and paste-like media in open or closed containers and unaffected by possible foam formation. The integrated HistoROM/M-DAT data module makes management of process and device parameters easy. Designed according to IEC 61508 for use in SIL3 safety systems.

    • Hermetically sealed Contite measuring cell with condensate-resistance, high reference accuracy: ±0.1%, optionally ±0.075% and minimum temperature effects thanks to active temperature compensation
    • Best batch-to-batch repeatability and long-term stability
    • Modular concept for easy replacement of display or electronics
    • HistoROM/M-DAT data backup for instrument settings and measured values
    • Function-monitored from the measuring cell to the electronics
    • Seamless and independent system integration (HART/PA/FF)
    • International usage thanks to a wide range of approvals

    For level and/or pressure measurement.

    • Process connections: Threads, flanges and hygienic connections
    • Temperature: –10 to +100°C (14 to 212°F) (+135°C (275°F) for 30 minutes maximum)
    • Measuring range: 0.1 to 10 bar rel. (1.5 to 150 psi)
    • Accuracy: ±0.075%
    • International explosion protection certificates, overfill prevention WHG, SIL, hygienic certificates, marine approvals

     

    • Measuring principle

      Hydrostatic

    • Characteristic / Application

      Pressure transmitter for pressure or hydrostatic level measurement with flush mounted metallic CONTITE measuring cell: 
      – hermetically welded 
      – absolute condensation tight 
      – climate-resitant 
      – long-term stable 
      – Lowest temperature influences 

      Compact version 
      Modular Deviceplatform

    • Specialities

      Diagnostic functions

    • Supply / Communication

      4…20mA HART:
      10,5…45V DC
      Ex ia: 10,5…30V DC
      PROFIBUS PA /
      FOUNDATION Fieldbus:
      9…32V DC (Non Ex)

    • Accuracy

      Standard 0,1% 
      Optional 0,075%

    • Long term stability

      0,05% of URL/year

    • Ambient temperature

      -40°C…85°C 
      (-40°F…185°F)

    • Process temperature

      -10°C…100°C
      (14°F…212°F)

    • Process pressure absolute / max. overpressure limit

      40 bar (600 psi)

    • Pressure measuring range

      100mbar…10bar 
      (1.5psi…150psi)

    • Main wetted parts

      Alloy C
      316L

    • Process connection

      Thread:

      G1 1/2, MNPT1/2

      Flange:

      DN40…DN100,

      ASME 1 1/2″…4″,

      JIS 10K

    • Process connection hygienic

      Tri-Clamp

      DIN11851

      DIN11864-1

      NEUMO

      Varivent N

      SMS

      DRD

    • Max. measurement distance

      100m (328ft) H2O

    • Communication

      4…20 mA HART
      PROFIBUS PA
      FOUNDATION Fieldbus

    • Certificates / Approvals

      ATEX, FM, CSA, CSA C/US, IEC Ex, INMETRO, NEPSI, EAC

    • Safety approvals

      Overfill prevention WHG

      SIL

    • Design approvals

      EN10204-3.1

      NACE MR0175, MR0103

    • Hygienic approvals

      3A, EHEDG

      CoC ASME-BPE

    • Marine approval

      GL/ DNV

    • Drinking water approvals

      NSF

    • Options

      HistoROM/M-Dat
      4-line digital display
      SS- or Aluminiumhousing

      Separate housing

    • Application limits

      Measuring cell: Contite, 
      condensate-proof, watertight, 
      metal welded

      If pressurized, possibly use 
      differential pressure measurement 
      with two pressure 
      transmitters. Observe ratio 
      head pressure : hydrostatic 
      pressure

    Datasheet: Weld-in adapter, process adapter and flanges

    Deltapilot S FMB70 Technical Information

    Scroll to Top
    ×