fbpx
Last Updates: 12/09/2020
Brands:Baumer

Baumer FlexTop 2202 Temperature Transmitter

$67

Part Number: FlexTop 2202 Categories: ,

Email Us: sales@celectric.com.my
WhatsApp Us: +60165519084

Type: [02] Pt100 in / 4-20 mA out, ±0,25°C
Safety: [0001] Standard
Configuration: [0] None
$67

Availability: 28 in stock

Baumer FlexTop 2202 is a 4 to 20 mA loop-powered temperature transmitter for Pt100 temperature sensors either 2, 3 or 4-wire sensors. For 2-wire sensors, auto-balancing of the sensor cable resistance is possible with shorted sensor cable. The cable resistance can be manually configured as well by using a PC, the Windows-based Flex-Program with a FlexProgrammer configuring unit. The configurations of the following parameters can be possible via the output connectors (2-way communication):

  • TAG no
  • Number of wires
  • Cable resistance
  • Error detection level
  • Measuring range/unit
  • Damping
  • Offset
  • Status indication.

The Baumer FlexProgrammer 9701 with data logging facility enabling the user to monitor measuring results or calibrate the measuring setup.
Baumer FlexTop 2202 is embedded in silicone which makes it resistant to humid environments also fitting into the DIN B housing, has a 6 mm centre hole for quick sensor replacement. Spring-loaded mounting screws ensure a safe fastening even in vibrating environments.

  • Specifically for Pt100
  • Input: Pt100 2-, 3- or 4-wires
  • Configurable range -200 … +850 °C
  • Accuracy +/- 0.25 °C
  • ATEX explosion protection
  • DIN form B housing installation
Ambient conditions
Degree of protection (EN 60529)
  • IP 40
Humidity
  • < 98 % RH , condensing
Long-term test (transmitter)
  • IEC 770 6.3.2
Vibration (sinusoidal) (EN 60068-2-6)
  • 1.6 mm p-p (2 … 25 Hz), 4 g (25 … 100 Hz), 1 octave / min.
Output signal
Damping
  • 0.0 … 30 s , programmable
Output signal
  • 4 … 20 mA , 2-wire
Accuracy
  • < 0.1 % FSR
Temperature drift
  • < 0.003 %/K , typ.
  • < 0.01 %/K , max.
Load resistance
  • R = (U – 8 V)/23 mA
Resolution
  • 12 bit
Up/Down scaling limits
  • 23 mA / 3.5 mA
Ripple immunity
  • 3 Vrms
Power-up time
  • ≤ 10 s
Power supply
  • 8 … 35 V DC
Reverse polarity protection
  • Yes
Effect of variations in supply voltage
  • < 0.01 %/V
TAG No.
  • 15 characters
Compliance and approvals
EMC
  • EN 61000-6-2
  • EN 61000-6-3
  • EN 61326-1
Namur
  • NE21
Explosion protection
  • ATEX II 1G Ex ia IIC T5/T6
  • ATEX II 3G Ex nA IIC T5

Datasheets: Baumer_FlexTop-2202-datasheet
Manuals: Baumer_FlexTop_2202-manual